What is the pin assignment of the KPG3-PS3 cable ?

 
  • Click on the question to obtain information.


How can you connect the outputs in parallel on the LE4-116-DD1 and LE4-116-XD1?

 
  • Only the outputs of the same driver should be connected in parallel.


How can you connect a PROFIBUS-DP master and a PROFIBUS-DP slave to the PS4-341-MM1 together?

 
  • Click on the question to obtain information.


What is the current hardware version of the PS3AC and PS3DC ?

 
  • The current hardware version (12/2000) of the PS3AC and PS3DC is : Version 1.7


How is the hardware counter in the PS4-341-MM1 activated and programmed ?

 
  • The PS4-341-MM1 counter is activated and assigned parameters in the Sucosoft S40 Topology Configurator.


What temperature monitoring options are available with the PS4 / PS416 system?

 
  • EM4-101-TX1, EM4-101-TX2 remote expansion modules and the PS4-271-MM1 PLC offer temperature measuring features.


How do you implement the short-circuit monitoring of the outputs on the
PS416-OUT-400 / -410 cards ?

 
  • Use a ZAA central monitoring unit


Is the NG31 still available or is there a similar substitute ?

 
  • A substitute can be obtained directly from the company Hubert Schröter. Click the question to obtain information.


Does the Moeller automation product range include an SSI interface for absolute positioning encoders ?

 
  • The LE4-633-CX1 local expansion module is available for this


How can you implement a connection between an EPC335 card and a PS4?

 
  • Use the KPG3-PS3 cable. Order No.: 014487


How can you map a larger number of I/O to the marker range ?

 
  • Use the


Can I use the PS416-CPU in the PS316 rack with its I/O cards ?

 
  • Neither the rack nor the I/O-cards of the PS316 series can be used.


What is the successor of the EM4-101-AA1 ?

 
  • The successor is the EM4-101-AA2


What settings are required to connect an MI4 to a PS4-341 via Suconet K ?

 
  • a) Check MI4 configuration
    b) Check PLC Topology Configurator


Can the PS4-341-MM1 emulate the Sucom-A of the PS316 ?

 
  • Yes, with the PS4-341-MM1 operating system from Sucosoft S40 version 4.0


What is necessary to actuate a contactor coil as an emergency measure when the PLC malfunctions ?

 
  • Decoupling via a protective diode


Is it possible to change the analog output of the PS4-271 from a 0-10 V to a 0-20 or 4-20 mA signal using an 500 Ohm resistor ?

 
  • No, since only 5 mA is provided at the analog output.


How can you prepare your own Suconet K/K1 cable ?

 
  • Use LT309.096 cable and connector S1-PS3.


How can PLCs be provided with serial interfaces ?

 
  • The ZB4-501-UM3 and ZB4-501-UM4 interface converters can be used for this purpose


How can closed-loop control tasks be implemented with the PS4/PS416 PLC systems ?

 
  • There are two application modules with two-point controllers, three-point controllers, PID controllers and there is a closed-loop control toolbox for complex closed-loop control.


How can the PS4/PS416 system receive and evaluate the DCF77 radio time signal ?

 
  • A DCF77 receiver is required for receiving the DCF77 radio time signals and a software is required for evaluating the signal.


Is it possible to carry out remote diagnostics for the PS4/PS416 system ?

 
  • Remote diagnostics can be carried out using a modem connection between the programming device and the PLC.


Is it possible to run a Suconet K2 line with the PS416 ?

 
  • The PS416-NET-210 Suconet K1/K2 card and the S40-AM-K2-D/GB application module are required for running Suconet K2 with the PS416.


Which memory module version can be used in the PS4-341-MM1 as a space ?

 
  • Note: verify PS4-341-MM1 version number.


Can the Sucom_A functionblock be used on the PS4-... MM1 in order to program the PLC with Sucosoft S40 ?

 
  • No


Which PS4 type can be equipped with the PROFIBUS-DP master module ?

 
  • Only the PS4-341-MM1.


What is the type designation of the spare memory module for the ZB4-901-SF1 ?

 
  • ZB4-901-SF2


How many LE4-505-BS1 and CM4-505-GS1 AS-Interface masters can be connected to a PS4-... ?

 
  • Click on the question to obtain information.


How can PS4 compact PLCs be expanded locally?

 
  • The PS 4 compact PLCs are expanded with LE4-. . . expansion modules.


What design measures are required to integrate an LE4-504-BT1 (PROFIBUS-DP Slave) in a STEP 7 hardware configuration?

 
  • The design measures for integrating an LE4-504-BT1 (PROFIBUS-DP Slave) in a STEP 7 hardware configuration are shown in a video that can be downloaded.


How can PS4/PS416 systems be networked with PROFIBUS-FMS?

 
  • Different modules/cards are available for networking PS4/PS416 systems with PROFIBUS-FMS. Click the question to obtain further information.


How can the PS416 networked with PROFIBUS-PA?

 
  • The PS416 can be networked with PROFIBUS-PA using a segment coupler.


How are PS416 systems networked using the PS416-NET-400 Suconet K network card?

 
  • Click the question above to obtain a description of the networking of PS416 systems.


Can the CoBox also be run on the Suconet (RS485) interface?

 
  • On the PS4-341-MM1 the CoBox can also be run directly on the Suconet interface if the SucomA function block is called in Transparent mode.


Can the PS4/PS416 communicate via Ethernet ?

 
  • For the communication with Ethernet is the network-module ″COBOX″ available.


Can the PS4-151-MM1 be mounted and run in a vertical position?

 
  • Yes, the vertical mounting position is possible if the interfaces (PRG / Suconet) are towards the bottom.


Which PS416 cards can be used in the PS316 ?

 
  • The following PS416 cards were tested and released for the PS316 series:
    PS416-INP-400, PS416-INP-401
    PS416-OUT-400, PS416-OUT-401


Which PLC types can be connected to the S40-OPC-Server as clients ?

 
  • PS4-141/-151/-201/-271/-341-MM1as well as the PS416


Which connection interfaces are possible for connection between the PC (S40-OPC-Server) and PLC (Clients) ?

 
  • Click the question to obtain further information.


How can the analog values of the potentiometers on PS4 controllers be converted to TIME type variables?

 
  • Click the question to obtain further information.


What is the application module required for data exchange between the PS40 controller via Ethernet?

 
  • The application module is: S40-AM-K5-GB, to download please click on the question.


What hardware (PLC) can be used with the Positioning Toolbox ?

 
  • PS4-341-MM1 and PS416


Where are the version lists for Moeller PS4/PS416, EM4, LE4, Sucosoft and MI4/MV4 ?

 
  • With clicks the question you reach the current version lists.


What is the application module for Ethernet data coupling with the
PS4-150/-200/-341 and PS416 ?

 
  • Yes, the application module S40-AM-K5-GB. With clicks the question to download.


What has to be observed when a PS416-MEM-442 or PS416-MEM-443 memory module is ordered ?

 
  • See answer!


Which LE4-... modules have a CSA approval (Status: November 2001) ?

 
  • All the LE4-... modules which are in the Main Catalogue 2002: Automatisierungstechnik, Antriebstechnik have CSA approval.


How high is the level of input impedance with the PS4-..., LE4-..., EM4-100/200 and the PS416-INP400/401 input module ?

 
  • With the PS4-..., EM4-... and PS416-... the input impedance is 6.5 kOhms, with LE4-... the input impedance is 4.1 kOhms


What is the permissible power supply range for the PS4-.../EM4-... and LE4-... devices ?

 
  • With 24V power supply (DC), from 20.4 to 28.8 V
    With 115 to 230 V power supply (AC): from 98 to 264 V


What is the correct course of action when diagnostics status message:
″ Unexpected Type ″

 
  • Please check the version number, the version 01 or 03 and higher is o.k.


What should be done when the data exchange between the central cards of a PS416 and the CPU from S40 version 4.12 is not consistent (data from different cycles) ?

 
  • You need the new operation system OS 416M_410.


Is there an update for the closed-loop control toolbox ?

 
  • Yes, please click on the question to reach the download.


How do you declare a function block in S40 as retentive ?

 
  • Please click on the question to obtain further information.


Can a PS4 or PS416 program be SAVED/RESTORED (packed/unpacked) ?

 
  • Yes, with the function: SAVE in the S40 navigator.


How many inputs are available on the EM4-101-AA2 in Suconet K mode ?

 
  • In Suconet K mode there is no restriction. All 4 voltage and 4 current inputs are available. The allocation to the input address is shown in table 4-24 in the documentation AWB27-1257D.


Are WINbloc and XI/ON protected against incorrect plug connection ?

 
  • Yes, for every WINbloc and XI/ON electronic module, we provide coding elements that can be used if required.


With which European EMC standard does WINbloc comply ?

 
  • WINbloc interference immunity complies with EN 50082-1 and -2.


How are the XI/ON modules coded?

 
  • The modules are self-coding. This is done by fitting the card (electronic module) in the base unit.


What terminals are used with XI/ON ?

 
  • Screw or tension clamp terminals are used with XI/ON.


Is the size of XI/ON smaller than competitor products ?

 
  • Yes, XI/ON input/output modules (slices) are 12.5 mm wide. Most competitor modules, such as Siemens, have a width of 15 mm.


What are the maximum number of digital and analog modules (channels) ?

 
  • The maximum number of digital channels is 256 per station and 64 analog channels per station.


What is the assignment of the four-wire terminal base module ZS 41.5/16 S/S/PE-+UI with the WINblock module DP-4AAI/UI ?

 
  • Please click on the question to obtain further information.


Can I use only Input slices on a PROFIBUS-DP XI/ON XSystem Remote Gateway ?

 
  • No. Please click on the question to obtain further information !


How do you read or write the inputs and outputs of the PS4 controller directly?

 
  • With direct peripheral access. Please click on the question to obtain further information !


How do you determine the reaction time of a PS4 controller?

 
  • By adding together the input delay, maximum PLC cycle time and output delay. Please click on the question to obtain further information!

 

 

 

.
 
 

 

 