The historic diagnostics is saved in the gateway. This memory is sufficient for 20 entries that can be saved for up to 24 days. Each new diagnostics report removes the oldest one from the memory. A voltage interruption has the effect of a reset.
In the device menu select from the main menu:
Device => Network =>IP address.
The device must be restarted once the ip address has been changed.
The restart takes place automatically by returning to the main menu via ENTER.
A maximum of 20 XStart modules can be used as DOL starters without trip-indicating auxiliary contacts in an XI/ON station. With a trip-indicating auxilary contact and reversing starters with / without trip indication, the maximum number is only 10.
Check that all basic modules are making correct contact. Always push the basic modules tightly together, and use end brackets on the top-hat rail for fixing.