Using the temperature modules MFD-TP…/MFD-TAP…
you can now directly connect PT100
and NI1000 temperature sensors
directly to the MFD-Titan. Thus, the
indirect method utilising an
expensive temperature measurement
amplifier is avoided.
The temperatures are measured with a
12 bit resolution and can be
assigned to temperature ranges from
-200 °C to 850
°C.

You
also have the option of selecting
2-wire or 3-wire connection of
temperature sensors.
Programming is implemented in the
usual manner using the wiring
diagram entry via the EasySoft
programming software.
Technical data
|
Analog inputs for Pt100 or
Ni1000 resistance temperature
sensors |
|
Quantity |
2 x Pt100 or 2 x Nt1000
(depending on the type) |
Resistance sensor input type
|
|
– Platinum sensor Pt100
according to
DIN EN 60751, IEC 751
|
|
– Nickel sensor Ni1000 according
to
DIN 43760 |
|
|
Temperature ranges |
|
|
– Pt100, range A, selectable |
°C, (°F) |
-40 to +90, (-40 to 194); 0 to
250,
(32 to 482); 0 to 400, (32 to
752) |
|
– Ni1000, range A, selectable |
°C, (°F) |
-40 to +90, (-40 to 194); 0 to
250, (32 to 482) |
|
– Pt100, range B |
°C, (°F)
|
0 to 850, (32 to 1562); -200 to
200,
(-328 to 392) |
|
Digital resolution, scaling per
sensor |
|
– With operand „IA“ and „MD“,
selectable under scalling |
Bit |
12 (0 to 4095) |
– With operand "MD",
selectable under scaling |
°C, (°F)
|
1, 0,1, (1), (0,1) |
|
Measurement method |
Selectable two wire or three
wire per sensor, using the
sensor connections |
|
Here you find your