Residual-current circuit-breaker
Residual-current protection module
The residual-current protection modules can be connected to
the bottom of the circuit-breaker NZM1 and NZM2 (on the NZM1
on the right) with the same contour design.
This device
combination fulfils the following tasks:
– conduct and switch current up to 250 A
– protection with overload, short-circuit and fault current.
A compact and
mounting-friendly solution!
Alternatively
the modules can be combined with switch-disconnectors N. An
external auxiliary voltage is not required. The
residual-current protection module of the NZM2 is
independent of the mains voltage and can thus be used for
personnel protection in Germany.
You can select
between pulse current sensitive and AC/DC sensitive devices.
There are 3 and 4-pole devices featuring different rated
fault currents available for almost every mains
constellation: from 30 mA to time-discriminating 3 A.
In the event of
a fault the residual-current-operated circuit-breaker on the
NZM1 will initially indicate the rising fault current via an
LED. Only when the adjusted fault current is exceeded will
the residual-current release of the circuit-breaker trip.
This means: the main contacts are opened. The cause of the
trip is indicated mechanically on the NZM1 and 2.
Optional
auxiliary contacts can be clipped on in order to remotely
indicate the trip. The circuit-breaker and the
residual-current release must be reset and switched back on
in order to restore the power supply.
PFR Residual
Current Relay with Ring-Type Transducer –
Flexible fault current protection up to 1800 A current
rating
 Compact,
safe, adaptable...
... just as it should be, the fault current protection which
is particularly suited for cramped spaces such as for
example in service distribution systems.
Ring-type
transducers which are arranged in a space saving manner on
the cabling run and the measuring relay which is simply
snapped onto the DIN mounting rail, combine to form a
functional unit.
The new Moeller
relay/transducer combination covers operating currents in a
range from 1 to 1800 A. The wide spectrum of applications
ranges from general power distribution tasks to individual
motor controls.
The fault currents which are detected and processed by the
relay range from 30 mA to 5 A.
Residual Current Relay with Ring-Type Transducer
|
 |
 |
Fault current relay |
|
Ring-type transducer |
The adjustable
relay provides a pre-warn function which alerts before the
set fault current is exceeded. The pre-warning allows
preventative action to be taken to prevent shutdown of the
electrical energy.
 |